SCG PCIF Pipe Insulation
Price 90.00 บาท – 905.00 บาทPrice range: 90.00 บาท through 905.00 บาท
Product Details
SCG PCIF Pipe Insulation is manufactured from high-density fiberglass (64 kg/m³), heat resistant up to 540oC, molded into pipe sections according to steel pipe sizes and faced with aluminum foil to prevent moisture and fiber release
SCG PCIF comes in pipe sizes from 0.5″ to 18″ with insulation thickness from 25-100mm. Pre-slit lengthwise for easy installation, reducing installation time and labor costs
Hot water piping systems distribute water throughout buildings for various uses, such as in hotels and food industries where hot water or steam is commonly used. The pipes must be insulated to maintain temperature until the endpoint
Product List
PCI
SCG Industrial Insulation for hot and cold water pipes, PCI model, is made from fiberglass molded into rigid pipe sections according to steel pipe sizes
PCIF
SCG Industrial Insulation for hot and cold water pipes, PCI model, is fiberglass molded into rigid pipe sections according to steel pipe sizes, faced with reinforced aluminum foil 3-way non-flammable, tested to BS 476 and ASTM E84 standards
SCG Pipe Insulation Size Chart
|
Pipe Size (NPS) |
Internal Diameter Pipe Insulation (Internal Diameter pipe Insulation) |
Insulation Thickness (mm) |
|
0.5 |
22 |
25, 38, 50, 63, 75, 100 |
|
0.75 |
27 |
25, 38, 50, 63, 75, 100 |
|
1 |
34 |
25, 38, 50, 63, 75, 100 |
|
1.25 |
43 |
25, 38, 50, 63, 75, 100 |
|
1.5 |
49 |
25, 38, 50, 63, 75, 100 |
|
2 |
61 |
25, 38, 50, 63, 75, 100 |
|
2.5 |
74 |
25, 38, 50, 63, 75, 100 |
|
3 |
90 |
25, 38, 50, 63, 75, 100 |
|
3.5 |
102 |
25, 38, 50, 63, 75, 100 |
|
4 |
115 |
25, 38, 50, 63, 75, 100 |
|
4.5 |
128 |
25, 38, 50, 63, 75, 100 |
|
5 |
143 |
25, 38, 50, 63, 75, 100 |
|
6 |
170 |
25, 38, 50, 63, 75, 100 |
|
7 |
196 |
25, 38, 50, 63, 75, 100 |
|
8 |
221 |
25, 38, 50, 63, 75, 100 |
|
9 |
246 |
25, 38, 50, 63, 75, 100 |
|
10 |
275 |
25, 38, 50, 63, 75, 100 |
|
12 |
324 |
25, 38, 50, 63, 75, 100 |
Technical Data Table
|
Features |
Technical Specifications |
Test Standard |
| Water Vapor Absorption |
0.2 % by volume |
ASTM C1104 |
| Mold and Fungus Growth |
Does not promote mold and fungus growth |
ASTM C665 |
| Surface Burning on Insulation |
Flame Spread < 25 |
ASTM E84 |
Thermal Conductivity Table
|
Mean Temperature (C) |
Thermal Conductivity (W/m.K) |
|
10 |
0.030 |
|
24 |
0.032 |
|
38 |
0.035 |
|
66 |
0.039 |
|
93 |
0.043 |
|
121 |
0.046 |
|
149 |
0.055 |
|
177 |
0.058 |
|
204 |
0.063 |
|
232 |
0.069 |
|
260 |
0.078 |
Installation Guidelines
- For pipe insulation installation, order appropriate sizes using internal diameter for steel pipes (Pipe Size) and external diameter for other metal pipes (Tube Size)
- Install insulation around pipe, slightly notching the inner edge lengthwise for easier fitting
- Cover insulation with stainless jacket or aluminum foil to reduce heat transfer. Using dark surface materials or paint helps reduce surface temperature in high-heat systems and prevents condensation
- For additional insulation thickness, order using the outer diameter of the existing insulation