SCG PCI Glass Fiber Pipe Insulation

Price Price range: 80.00 บาท through 845.00 บาท

Product Details

SCG PCI Glass Fiber Pipe Insulation is made from high-density glass fiber (64 kg/m³), heat resistant to 540oC, molded to fit steel pipe sizes, with low thermal conductivity to maintain pipe temperature, non-combustible

SCG PCIF comes in pipe sizes from 0.5″ to 18″ with insulation thickness from 25-100mm. Pre-slit lengthwise for easy installation, reducing installation time and labor costs

Hot water piping systems distribute hot water throughout buildings for various uses, such as in hotels and food industries where hot water or steam is essential. The pipe systems require insulation to maintain temperature until the endpoint

Pipe-shaped glass fiber insulation has a density of 64 kg/m³ to maintain shape and ease installation. It can withstand temperatures from normal to 540°C. For higher temperatures, rock wool insulation is more suitable, but below 540°C, glass fiber is more cost-effective with similar efficiency

Product List

PCI

SCG PCI Glass Fiber Pipe Insulation for industrial hot and cold water pipes is molded to fit standard steel pipe sizes

{%ALT_TEXT%}

{%CAPTION%}

PCIF

SCG PCIF Glass Fiber Pipe Insulation for industrial hot and cold water pipes is molded to fit steel pipe sizes, covered with reinforced aluminum foil in 3 directions, fire-resistant on one side, tested to BS 476 and ASTM E84 standards

SCG PCIF Glass Fiber Pipe Insulation for hot water pipes

SCG PCIF Glass Fiber Pipe Insulation for hot water pipes

Product Size Table

Pipe Size (NPS)

Internal Diameter Pipe Insulation

(Internal Diameter pipe Insulation)

Insulation Thickness (mm)

0.5

22

25, 38, 50, 63, 75, 100

0.75

27

25, 38, 50, 63, 75, 100

1

34

25, 38, 50, 63, 75, 100

1.25

43

25, 38, 50, 63, 75, 100

1.5

49

25, 38, 50, 63, 75, 100

2

61

25, 38, 50, 63, 75, 100

2.5

74

25, 38, 50, 63, 75, 100

3

90

25, 38, 50, 63, 75, 100

3.5

102

25, 38, 50, 63, 75, 100

4

115

25, 38, 50, 63, 75, 100

4.5

128

25, 38, 50, 63, 75, 100

5

143

25, 38, 50, 63, 75, 100

6

170

25, 38, 50, 63, 75, 100

7

196

25, 38, 50, 63, 75, 100

8

221

25, 38, 50, 63, 75, 100

9

246

25, 38, 50, 63, 75, 100

10

275

25, 38, 50, 63, 75, 100

12

324

25, 38, 50, 63, 75, 100

Technical Data Table

Features

Technical Specifications

Test Standard

Water Vapor Absorption

0.2 % by volume

ASTM C1104

Mold and Fungus Growth

Does not promote mold and fungus growth

ASTM C665

Surface Burning on Insulation

Flame Spread < 25
Smoke Develop < 50

ASTM E84

Thermal Conductivity Table

Mean Temperature (C)

Thermal Conductivity

(W/m.K)

10

0.030

24

0.032

38

0.035

66

0.039

93

0.043

121

0.046

149

0.055

177

0.058

204

0.063

232

0.069

260

0.078

Installation Guidelines

  1. For pipe insulation installation, order appropriate sizes using internal diameter for steel pipes (Pipe Size) and external diameter for other metal pipes (Tube Size)
  2. Install insulation around pipe, slightly notching the inner edge lengthwise for easier fitting
  3. Cover insulation with stainless jacket or aluminum foil to reduce heat transfer. Using dark surface materials or paint helps reduce surface temperature in high-heat systems and prevents condensation
  4. For additional insulation thickness, order using the outer diameter of the existing insulation

Additional Products / Related Products