SCG Glass Wool Insulation for High Temperature with Single-sided Foil, HTIF Model

Price Price range: 780.00 บาท through 4,880.00 บาท

Product Details

SCG glass wool insulation for high-temperature applications, used in industrial processes up to 540°C including hot steam, hot water pipes, and food industry. Glass wool insulation is preferred due to its cost-effectiveness and good performance.

Heat Insulation for High Temperature Applications

In high-temperature industrial applications not exceeding 540°C, including hot steam, hot water pipes, and food industry, glass wool insulation is commonly used as thermal insulation due to its cost-effectiveness and good performance.

OVEN

The steel industry requires high temperatures, necessitating glass wool insulation for heat protection.

Product List

HTI

SCG Industrial Heat Insulation for high-temperature applications, HTI model, unfaced type. Glass wool insulation available in rolls and boards, without facing material, tested to BS 476 standard.

HTIF

SCG Industrial Heat Insulation for high-temperature applications, HTIF model, with single-sided aluminum foil facing. Glass wool insulation available in rolls and boards, faced with fire-resistant tri-directional reinforced aluminum foil on one side, tested to BS 476 and ASTM E84 standards.

HTIFD

SCG Industrial Heat Insulation for high-temperature applications, HTIFD model, with double-sided aluminum foil facing. Glass wool insulation available in rolls and boards, faced with fire-resistant tri-directional reinforced aluminum foil on both sides, tested to BS 476 and ASTM E84 standards.

High-Temperature Glass Wool Insulation Roll Dimensions Table

Density (Kg/m3)

Thickness (mm)

Size (W x L)

16

50

1.22 x 15.25

26

50

1.22 x 15.25

32

50

1.22 x 15.25

75

1.22 x 7.50

High-Temperature Glass Wool Insulation Board Dimensions Table

Density (Kg/m3)

Thickness (mm)

Size (W x L)

32

50

1.22 x 2.44

75

1.22 x 2.44

38

50

1.22 x 2.44

75

1.22 x 2.44

Technical Data Table

Features

Technical Specifications

Test Standard

Water Vapor Absorption

0.2 % by volume

ASTM C1104

Mold and Fungus Growth

Does not promote mold and fungus growth

ASTM C665

Surface Burning on Insulation

Flame Spread < ≤ 25
, Smoke Develop < ≤ 50

ASTM E84

Insulation Thermal Conductivity Table

Mean Temperature

(Operating Temp + Outside Temp) /2

Degree Celsius (°C)

Thermal Conductivity (W/m.K)

16K

26K

32K

38K

10

0.035

0.033

0.031

0.030

24

0.038

0.035

0.033

0.032

38

0.041

0.038

0.037

0.035

99

0.052

0.049

0.048

0.043

149

0.078

0.067

0.060

0.055

204

0.108

0.089

0.075

0.063

260

0.149

0.119

0.103

0.089

316

0.203

0.160

0.135

0.114

Heat Loss (W/m²) and Surface Temperature (°C) Table for Various Thicknesses of HTI Glass Wool Insulation

Insulation Thickness

Insulation Thickness (mm)

Operating Temperature (°C)

250

350

425

540

HL

ST HL ST HL ST HL

ST

HTI 16K

25

512

118 887 167 1575 248 2581

356

50

292

86 515 118 954 175 1664

258

75

204

72 360 97 674 140 1200

205

100

156

64 277 84 520 119 932

172

125

127

59 225 76 422 106 760

151

150

107

56 189 70 355 96 641

136

275

92

53 163 66 307 88 554

124

200

81

51 143 62 270 83 488

114

HTI 26K

25

446

109 760 151 1345 222 2231

319

50

251

80 431 99 784 154 1361

224

75

174

68 300 82 548 123 963

176

100

134

61 230 72 420 105 742

148

125

108

56 186 66 341 94 602

130

HTI 32K

25

405

103 679 140 1190 203 1979

293

50

226

76 381 99 679 141 1167

201

75

157

64 264 82 472 113 818

258

100

120

58 202 72 362 97 628

133

125

97

54 164 66 293 87 509

118

HTI 38K

25

364

97 601 130 1047 187 1745

267

50

201

72 334 93 587 128 1001

181

75

140

62 231 77 406 103 696

142

100

107

56 176 68 310 89 532

121

125

86

52 143 62 251 80 431

107

Additional Products / Related Products