SCG Glass Wool Insulation for Air Conditioning Systems, Single-sided Foil FRK-G Model
Price 1,950.00 บาท – 4,900.00 บาทPrice range: 1,950.00 บาท through 4,900.00 บาท
Product Details
SCG thermal insulation for air conditioning systems, FRK-G model duct insulation with single-sided fire-retardant tri-directional reinforced aluminum foil, tested to BS 476 and ASTM E84 standards
SCG Glass Wool Insulation for Air Conditioning Systems
Duct Insulation Work
Large air conditioning systems consisting of chillers and Air Handling Units (AHU) require galvanized air ducts to distribute cool air to desired points. To maintain air temperature, heat insulation must be installed to prevent cold air leakage. It also provides soundproofing benefits. Typically, glass wool insulation used in air conditioning duct systems has a density of 24 kg/m³, with thickness options of 1 inch (25 mm) or 2 inches (50 mm), depending on requirements and installation space.
Product List
FRK-G
SCG thermal insulation for air conditioning systems, FRK-G model duct insulation with single-sided fire-retardant tri-directional reinforced aluminum foil, tested to BS 476 and ASTM E84 standards
FRKF-G
SCG thermal insulation for air conditioning systems, FRKF-G model duct insulation with double-sided fire-retardant tri-directional reinforced aluminum foil, tested to BS 476 and ASTM E83 standards
|
Density (kg/m³) |
Thickness (mm.) |
Size |
Thermal Conductivity (K-value) |
|
16 |
25 |
1.22 x 30.50 |
0.038 |
|
16 |
38 |
1.22 x 30.50 |
0.038 |
|
16 |
50 |
1.22 x 15.25 |
0.035 |
|
24 |
25 |
1.22 x 30.50 |
0.035 |
|
24 |
38 |
1.22 x 15.25 |
0.035 |
|
24 |
50 |
1.22 x 15.25 |
0.035 |
|
32 |
25 |
1.22 x 15.25 |
0.033 |
|
32 |
38 |
1.22 x 15.25 |
0.033 |
|
32 |
50 |
1.22 x 15.25 |
0.033 |
|
48 |
25 |
1.22 x 7.50 |
0.033 |
Installation Guidelines
- Duct surfaces must be clean, dry, rust-free, oil-free, and leak-free. Test all joints for leaks before insulating.
- Cut insulation to specified size and remove 50 mm of insulation from edges, leaving the facing material flap for overlap at joints.
- Wrap insulation around duct with tight joints, overlap the facing flap, and seal all joints with aluminum foil tape 2.5 inches or wider
- For ducts wider than 24 inches, use fasteners to secure insulation to the duct surface, spacing them no more than 18 inches apart on the bottom side
- Inspect facing material and seal any leaks, scratches, or tears with aluminum foil tape to prevent moisture and vapor accumulation in the insulation
|
Standard Thickness |
Average Installed Thickness |
Round Duct |
Square Duct |
Rectangular Duct |
|
1″ (25 mm) |
3/4″ (19 mm) |
P+7″ (178 mm) |
P+6″ (152 mm) |
P+5″ (127 mm) |
|
1-1/2″ (38 mm) |
1-1/8″ (28 mm) |
P+9-1/2″ (241 mm) |
P+8″ (203 mm) |
P+7″ (178 mm) |
|
2″ (51 mm) |
1-1/2″ (38 mm) |
P+12″ (305 mm) |
P+10″ (254 mm) |
P+8″ (203 mm) |
|
2.2″ (56 mm) |
1.65″ (42 mm) |
P+13″ (330 mm) |
P+11″ (279 mm) |
P+8-1/2″ (279 mm) |
|
3″ (76 mm) |
2-1/4″ (57 mm) |
P+17″ (432 mm) |
P+14-1/2″ (368 mm) |
P+11-1/2″ (292 mm) |
Technical Data Table
|
Features |
Technical Specifications |
Test Standard |
|
Water Vapor Absorption |
0.2 % by volume |
ASTM C1104 |
| Mold and Fungus Growth |
Does not promote mold and fungus growth |
ASTM C665 |
| Surface Burning on Insulation |
Flame Spread < ≤ 25 |
ASTM E84 |