SCG Glass Wool Insulation for Air Conditioning Systems, Double-sided Foil, Model FRKF-G
Price 2,800.00 บาท – 6,970.00 บาทPrice range: 2,800.00 บาท through 6,970.00 บาท
Product Details
SCG thermal insulation for air conditioning systems, FRKF-G model for duct insulation, covered with 3-way reinforced aluminum foil, non-flammable on both sides, tested according to BS 476 and ASTM E83 standards
SCG Glass Wool Insulation for Air Conditioning Systems
Duct insulation work
Large air conditioning systems consisting of chillers and Air Handling Units (AHU) require galvanized ductwork to distribute cool air to desired points. To maintain the temperature of the cool air, we must insulate the ducts to prevent cold air from escaping. This also helps reduce noise transmission. Typically, glass wool insulation with a density of 24 kg/m³ and thickness of 1″ (25 mm) or 2″ (50 mm) is used, depending on requirements and installation space.
Product List
FRK-G
SCG thermal insulation for air conditioning systems, FRK-G model for duct insulation, covered with 3-way reinforced aluminum foil, non-flammable on one side, tested according to BS 476 and ASTM E84 standards
FRKF-G
SCG thermal insulation for air conditioning systems, FRKF-G model for duct insulation, covered with 3-way reinforced aluminum foil, non-flammable on both sides, tested according to BS 476 and ASTM E83 standards
|
Density (kg/m³) |
Thickness (mm.) |
Size |
Thermal conductivity (K-value) |
|
16 |
25 |
1.22 x 30.50 |
0.038 |
|
16 |
38 |
1.22 x 30.50 |
0.038 |
|
16 |
50 |
1.22 x 15.25 |
0.035 |
|
24 |
25 |
1.22 x 30.50 |
0.035 |
|
24 |
38 |
1.22 x 15.25 |
0.035 |
|
24 |
50 |
1.22 x 15.25 |
0.035 |
|
32 |
25 |
1.22 x 15.25 |
0.033 |
|
32 |
38 |
1.22 x 15.25 |
0.033 |
|
32 |
50 |
1.22 x 15.25 |
0.033 |
|
48 |
25 |
1.22 x 7.50 |
0.033 |
Installation Guidelines
- Duct surfaces must be clean, dry, free of rust, oil residue, and leaks. Test for leaks at all points before insulating.
- Cut insulation to specified size, trimming 50 mm from the edges while leaving the facing material as a flap to overlap insulation joints.
- Wrap insulation around the duct with tight joints. Overlap the flap onto the other end of the insulation and use aluminum foil tape (2.5″ or wider) to seal all insulation joints.
- For ducts wider than 24″, use fasteners to secure insulation to the duct surface, attaching them to the bottom of the duct at intervals not exceeding 18″.
- Inspect the facing material. If leaks, abrasions, or tears are found, cover with aluminum foil tape to prevent moisture and vapor accumulation in the insulation.
|
Standard Thickness |
Average Installed Thickness |
Round Duct |
Square Duct |
Rectangular Duct |
|
1″ (25 mm) |
3/4″ (19 mm) |
P+7″ (178 mm) |
P+6″ (152 mm) |
P+5″ (127 mm) |
|
1-1/2″ (38 mm) |
1-1/8″ (28 mm) |
P+9-1/2″ (241 mm) |
P+8″ (203 mm) |
P+7″ (178 mm) |
|
2″ (51 mm) |
1-1/2″ (38 mm) |
P+12″ (305 mm) |
P+10″ (254 mm) |
P+8″ (203 mm) |
|
2.2″ (56 mm) |
1.65″ (42 mm) |
P+13″ (330 mm) |
P+11″ (279 mm) |
P+8-1/2″ (279 mm) |
|
3″ (76 mm) |
2-1/4″ (57 mm) |
P+17″ (432 mm) |
P+14-1/2″ (368 mm) |
P+11-1/2″ (292 mm) |
Technical Data Table
|
Features |
Technical Specifications |
Test Standard |
|
Water Vapor Absorption |
0.2 % by volume |
ASTM C1104 |
| Mold and Fungus Growth |
Does not promote mold and fungus growth |
ASTM C665 |
| Surface Burning on Insulation |
Flame Spread < ≤ 25 |
ASTM E84 |